What is the minimum number of sampling locations relating to the area of the cleanroom?

Last Updated:
ISO 14644-1:2015(E)

Table A.1 – Sampling Locations related to Cleanroom Area

Area of cleanroom (m2) less than or equal to Minimum number of sampling locations to be tested (NL)
2 1
4 2
6 3
8 4
10 5
24 6
28 7
32 8
36 9
52 10
56 11
64 12
68 13
72 14
76 15
104 16
108 17
116 18
148 19
156 20
192 21
232 22
276 23
352 24
436 25
636 26
1,000 27
> 1,000 See Formula (A.1)
Area of cleanroom (m2) less than or equal to Minimum number of sampling locations to be tested (NL)

 

Note 1: If the considered area falls between two values in the table, the greater of the two should be selected.

Note 2: In the case of unidirectional airflow, the area may be considered as the cross section of the moving air perpendicular to the direction of the airflow. In all other cases, the area may be considered as the horizontal plan area of the cleanroom or clean zone.